Specified Values
High-Pressure Side:
Increasing from initial pressure (when connecting the pressure gauges) to a maximum of 20 bar (290 psi).
Low-Pressure Side:
Decreasing from initial pressure (when connecting pressure gauges) to the value in the graph.
A - High pressure in bar
B - Low pressure in bar
C - Permissible tolerance range
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
Not enough refrigerant in circuit or expansion valve malfunctioning. | -- Extract refrigerant from the refrigerant circuit
|
If no malfunction can be found and the function of the A/C system is not correct after repeating the test, flush (clean) refrigerant circuit with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH R134A REFRIGERANT . If that is not possible in this workshop, flush the refrigerant circuit with compressed air and remove moisture with nitrogen. Refer to REFRIGERANT CIRCUIT, CLEANING WITH COMPRESSED AIR AND NITROGEN .
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
|
-- Run hand over refrigerant circuit to check for differences in temperature
|
If the function is not correct after flushing the refrigerant circuit, the expansion valve must be replaced.
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
|
-- Examine expansion valve for dirt or corrosion; replace if necessary.-- Flush refrigerant circuit with compressed air and nitrogen.-- Replace receiver/dryer.-- Repeat test if function is not OK.-- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH R134A REFRIGERANT .-- Charge the refrigerant circuit.-- Repeat the test. |
Always replace receiver/dryer in case of this malfunction.
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
|
-- Extract refrigerant from the refrigerant circuit
|
If the function of the A/C system is not correct when the test is repeated, re-install old expansion valve and flush refrigerant circuit with compressed air and nitrogen. Then replace A/C compressor and receiver/dryer.
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
|
-- Flushing the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH R134A REFRIGERANT .-- Replace the A/C compressor and receiver/dryer. |
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
|
-- Replace expansion valve-- Charge the refrigerant circuit.-- Repeat the test. |
If A/C system function is not OK when the test is repeated, flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH R134A REFRIGERANT . Then replace A/C compressor and receiver/dryer.
With this malfunction, evaporator may ice up although quantity of refrigerant in circuit is OK.
| Possible Deviation from Specification | Possible Cause of Fault | Corrective Action |
|---|---|---|
|
Too much refrigerant oil in the circuit. | -- Discharge the refrigerant circuit.-- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH R134A REFRIGERANT . |
|
Overfilling with refrigerant oil can occur if, for example, the A/C compressor was replaced without adjusting the quantity of refrigerant oil.
If the A/C compressor is not replaced, the refrigerant oil should be drained from the A/C compressor via the block connections. Out of the entire quantity of refrigerant oil, 50 grams should be put in the A/C compressor and the rest in the refrigerant circuit. Refer to the Vehicle-Specific Service Information.