A/C Compressor, Replacing Without Needing To Clean Refrigerant Circuit
Special tools and workshop equipment required
- This procedure is used, for example, with an external damage of the A/C compressor or an electric fault at the electrical A/C compressor.
- If there is no capacity information on the new A/C compressor. Refer to TECHNICAL DATA .
Procedure
-- Remove the A/C compressor. Refer to A/C COMPRESSOR, REMOVING AND INSTALLING .
-- Compare the type of refrigerant oil from the old and the new A/C compressor.
- If there are different types of refrigerant oil, then remove the refrigerant oil from the refrigerant circuit. In this case use the following procedure for replacing the A/C compressor. Refer to A/C COMPRESSOR, REPLACING DUE TO LEAKING OR INTERNAL DAMAGE .
Electric A/C Compressor
-- Determine the amount of refrigerant oil in the A/C compressor which is to be replaced (oil capacity 1 ) as follows:
- Drain the old refrigerant oil from the A/C compressor via both connections into a clean container. To ensure the best possible drainage, move the A/C compressor in a circular motion when draining.
- Weigh the collected refrigerant oil using the Digital Scale:VAS 231 007 .
- Remove any refrigerant oil still in the old A/C compressor, to do this, clean the A/C compressor. Refer to MAIN WIRING DIAGRAM, ELECTRICALLY-DRIVEN A/C COMPRESSOR, CLEANING .
- Determine the amount of oil 1 , for this, combine the weight of the drained and cleaned refrigerant oil.
- For 1 cm 3 refrigerant oil a weight of 1 g is presumed.
-- Check the drained refrigerant oil for discoloration and shavings.
- If a discoloration is determined (dark gray to black discoloration or shavings), then clean the refrigerant circuit and the A/C compressor. Refer to A/C COMPRESSOR, REPLACING DUE TO LEAKING OR INTERNAL DAMAGE .
-- Determine the refrigerant oil quantity to be removed from the new A/C compressor (oil quantity 2 ), as follows:
- Oil quantity 2 = oil quantity new A/C Compressor label - oil quantity 1
-- Drain the refrigerant oil not needed from the new A/C compressor (oil quantity 2 ) via the low-pressure side.
- For example: If a total of 60 cm3 refrigerant oil was removed from the faulty A/C compressor and the label of the new A/C compressor specifies a quantity of 200 cm3 , then 140 cm3 refrigerant oil must be drained from the new A/C compressor.
Mechanically Driven A/C Compressor
-- Drain the refrigerant oil from the faulty A/C compressor and measure the quantity.
- Remove the oil drain plug from the A/C compressor. Refer to LEAKING OR DAMAGED COMPONENTS, REPLACING, EMPTY REFRIGERANT CIRCUIT EXCEPT A/C COMPRESSOR AND RECEIVER/DRYER .
- To accelerate drainage of refrigerant oil, rotate the A/C compressor by way of clutch plate of A/C clutch, for example.
-- Remove the oil drain plug from the new A/C compressor and drain the refrigerant oil into a clean container. Refer to LEAKING OR DAMAGED COMPONENTS, REPLACING, EMPTY REFRIGERANT CIRCUIT EXCEPT A/C COMPRESSOR AND RECEIVER/DRYER .
-- Fill with the new refrigerant oil via the opening of the oil drain plug again. The quantity equals the quantity removed from the faulty A/C compressor.
Tip
- For example: If a quantity of 40 cm3 was removed from the faulty A/C compressor and 100 cm3 was removed from the replacement part compressor, then a quantity of 40 cm3 must be filled into the new A/C compressor. (The quantity of refrigerant oil removed from the new A/C compressor may be used).
-- After charging the refrigerant circuit, check the installed oil drain plug for leaks. Refer to LEAKS, FINDING USING ELECTRONIC LEAK DETECTOR .
Continuation for all vehicles
-- Assemble the refrigerant circuit.
-- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .
-- Start the A/C compressor. For this, perform the "Compressor cut-in, basic setting" function using the Vehicle Diagnostic Tester .