Emission Control System (2ZZ-GE): Inspection
- INSPECT VENTILATION VALVE SUB-ASSY
- Check the operation.
- Install a clean hose as shown in the illustration.
- Blow air into the cylinder head side, and check that the air passes through freely.CAUTION: Do not suck air through the ventilation valve. Petroleum substances inside the ventilation valve are harmful.
- Blow air into the intake manifold side, and check that the air does not pass through freely.
If the operation is not as specified, replace the ventilation valve.
- Check the operation.
- INSPECT FUEL TANK CAP ASSY
- Check the appearance.
- Visually check whether the fuel tank cap and gasket are deformed or damaged.
If necessary, repair or replace the cap and/or gasket.
- Visually check whether the fuel tank cap and gasket are deformed or damaged.
- Check the appearance.
- INSPECT CHARCOAL CANISTER ASSY
- Visually check the charcoal canister for cracks or damage.
If cracks or damage are found, replace the charcoal canister assy.
- Check charcoal canister operation.
- While holding the purge port closed, blow air at 1.67 kPa (17.0 gf/cm2
, 0.24 psi) into the vent port, and check that the air flows from the air inlet port.
If the result is not as specified, replace the charcoal canister assy.
- While holding the vent port closed, apply vacuum of 1.10 kPa (8.3 mmHg, 0.32 in.Hg) into the purge port, and check that the air flows from the air inlet port.
If the result is not as specified, replace the charcoal canister assy.
- While holding the purge port closed, blow air at 1.67 kPa (17.0 gf/cm2
, 0.24 psi) into the vent port, and check that the air flows from the air inlet port.
- Check the air leakage.
- Remove the air hose between ports A and B.
- Connect the pressure gauge to the vent port of the charcoal canister.
SST 09992-00242
- While holding port B, the purge port and the air inlet port closed and port A open, apply pressurized air at 19.6 kPa (0.2 kgf/cm2
, 2.81 psi) into the vent port, then confirm that the pressure is retained.
If the result is not as specified, replace the charcoal canister assy.
- Check leak detection pump.
- Check that air flows from port A to ports B and C. If the result is not as specified, replace the pump module.
- Apply battery positive voltage across the terminals.
- Check that the valve is closed.
If the result is not as specified, replace the pump module.
- Visually check the charcoal canister for cracks or damage.
- INSPECT VACUUM SWITCHING VALVE ASSY NO.1
- Check the resistance.
- Check the vacuum switching valve No. 1 for ground.
- Using an ohmmeter, check the resistance between each terminal and the body.
Standard:
TESTER CONNECTION AND SPECIFIED CONDITION (2 OF 4)Tester Connection Specified Condition 1 - Body 10M Ω or higher 2 - Body 10M Ω or higher If the resistance is not as specified, replace the vacuum switching valve No. 1.
- Using an ohmmeter, check the resistance between each terminal and the body.
- Check the operation.
- Check that air does not flow from port E to port F. If the operation is not as specified, replace the vacuum switching valve No. 1.
- Apply battery voltage across the terminals.
- Check that air flows from port E to port F.
If the operation is not as specified, replace the vacuum switching valve No. 1.
- INSPECT HEATED OXYGEN SENSOR
- Check the resistance. (Bank 1 Sensor 1)
- Check the resistance. (Bank 1 Sensor 2)