Electrical Leak Detector
Electrical Leak DetectorPRECAUTIONS FOR HANDLING LEAK DETECTOR
NOTE: When performing a refrigerant leak check, use a electronic refrigerant leak detector (J-41995) or equivalent. Ensure that the electronic refrigerant leak detector (J-41995) is calibrated and set properly according to the manufacturer's operating instructions.
The electronic refrigerant leak detector (J-41995) is a delicate device. To use the electronic refrigerant leak detector (J-41995) properly, read the manufacturer's operating instructions and perform any specified maintenance.
1. Position the probe approximately 5 mm (3/16 in) away from the point to be checked as shown.
2. When checking for leaks, circle each fitting completely with the probe as shown.
3. Move the probe along each component at a speed of approximately 25 - 50 mm (1 - 2 in)/second as shown.