LEMON Manuals: Even more car manuals for everyone: 1960-2025
Home >> Volkswagen >> 2017 >> e-Golf SE >> Repair and Diagnosis >> External Pages >> Different car >> Section 39 (Heating & Air Conditioning) >> 87 Air conditioning >> A/C refrigerant system, testing >> Checking
April 5, 2026: LEMON Manuals is launched! Read the announcement.

A/C refrigerant system, testing: Checking

WARNING: This page does not describe the selected car, but rather 17 other vehicles, including the 2009 Audi S4, 2009 Audi A4, 2008 Audi S4, 2008 Audi RS 4, and 2008 Audi A4. However, it is still accessible from the selected car via links, so may be relevant.
Ambient temperature in °C Displayed pressure (in bar absolute)
15 4.7
20 5.6
25 6.6
30 7.6
35 8.8
NOTE:
  • At absolute pressure, "0 bar" corresponds to an absolute vacuum. Normal ambient pressure thus corresponds to roughly " 1 bar " absolute. On the scales of most pressure gauges, "0 bar" corresponds to an absolute pressure of one bar (can be seen from "-1" mark below "0").
  • The pressure in the refrigerant circuit is governed by ambient temperature. Due to heat emitted by components (e.g. coolant fan), the pressure displayed with warm engine is slightly higher than that indicated for the relevant ambient temperature.
  • If the pressure displayed is lower than that given in the table, check measured value of High Pressure Sensor G65 → Read Measuring Value Block (function 08) "Reading measuring value block" and "Electrical checks, test step 5". If no malfunction is found at the High Pressure Sensor, there is not enough refrigerant in the circuit → Refrigerant R134a/Refrigerant Oil Capacities and Specifications

If pressure in refrigerant circuit is OK:

NOTE:
  • The A/C Compressor Regulator Valve N280 is activated by the operating and display module, Climatronic Control Module J255 such that the temperature of the air downstream of the evaporator reaches the specified value (approx. 2 to 5 °C). After starting the vehicle, a value greater than 75 % (0.55A) is displayed depending on measured temperature, engine speed and electrical system voltage. As soon as the temperature measured by the Evaporator Vent Temperature Sensor G263 approaches the specified value, activation is cancelled and compressor output thus reduced.
  • Under certain operating conditions, residual moisture in the coolant circuit may lead to the formation of ice at the compressor regulating valve. Such ice formation impairs compressor control, the evaporator is cooled excessively and ices up. Icing-up of the evaporator may give rise to the following problems:
  • - Repeated or sporadic failure of air conditioner (no cooling/heat output) after a long journey; air conditioner functions properly again after a short delay following engine shutoff.
  • - Misting up of windows on inside after a long journey; windows are initially not cleared even by pressing "Defrost" button; air conditioner functions properly again after a short delay following engine shutoff.
  • Remedy:
  • - Check measured value of Evaporator Vent Temperature Sensor G263 → Read Measuring Value Block (function 08) "Reading measuring value block", display group "010".
  • If the sensor measured value is too high under usage conditions described by customer (greater than e.g. 10 °C although air conditioner is functioning properly), check Evaporator Vent Temperature Sensor G263 (incorrect measured value can cause evaporator to ice up).
  • - If the sensor measured value is too low under usage conditions described by customer (colder than 0 °C for lengthy period at ambient temperature above 0 °C) although the A/C Compressor Regulator Valve N280 is not currently being activated, the vehicle must be taken to a dealership which services A/C systems.
  • - Check refrigerant line between evaporator and accumulator (thick line, low-pressure end) with engine running. If this line is severely iced up when the problem occurs (a thin layer of ice is permissible), this is also an indication that the temperature in the evaporator is too low.
  • - Make the air conditioner workshop aware of any problem encountered. The necessary work discharging of refrigerant circuit, replacement of and subsequent evacuation of refrigerant circuit for at least 3 hours.
  • - If display zone "1" shows no or insufficient current, check activation of A/C Compressor Regulator Valve N280 "Electrical checks, test step 6".
  • - If the pressure indicated in display zone "4" does not change and compressor activation is OK (display zones "1" and "2"), there is a malfunction in the refrigerant circuit → Refrigerant Circuit Repair Information
Fig 1: Evaporator Vent Temperature Sensor G263 Values Graph
GW00021358Courtesy of VOLKSWAGEN UNITED STATES, INC.

A - Air temperature measured by Evaporator Vent Temperature Sensor G263

B - Ambient temperature

C - Permissible tolerance range

Depending on ambient temperature, the measured air temperature must be within the stated tolerance range after 5 minutes.

NOTE:
  • If the required values are not attained, check measured value of Evaporator Vent Temperature Sensor G263. Compare measured values shown in display groups "010", zone "1" and "009", zones "3" and "4" :
  • - If the measured value in the two display zones "3" or "4" only differs slightly from the measured value in display group "010", perform "Corrective actions if readout does not match specification" → Identifying malfunctions if specified values are not obtained .
  • - If the measured value of the Evaporator Vent Temperature Sensor G263 is higher than that of the Left Vent Temperature Sensor G150 and the Right Vent Temperature Sensor G151, check proper installation of Evaporator Vent Temperature Sensor G263 and perform electrical check for this sensor "Electrical checks, test step 2".
  • Operation of the air conditioner can be established, for example, from cooling down of the refrigerant line on the "low-pressure end" (thick line).

If the measured value of the Evaporator Vent Temperature Sensor G263 (and thus the air conditioner cooling output) is OK:

After 5 minutes, the measured values in display group "009", zones "3" and "4" (Left Vent Temperature Sensor G150 and Right Vent Temperature Sensor G151) must not be more than 3 °C higher than the value in zone "1" of display group "010" (for Evaporator Vent Temperature Sensor G263).

NOTE:
  • If the required values are not attained, compare measured values indicated in display group "009", display zones "3" and "4" :
  • - If the measured value in one of the two display zones "3" or "4" is OK, check the temperature flap control motor for the side on which the measured value is not OK (Left Temperature Flap Motor V158 or Right Temperature Flap Motor V159) and perform electrical checks for Left Vent Temperature Sensor G150 and Right Vent Temperature Sensor G151 "Electrical checks, test step 2".
  • - If the measured value in display zones "3" or "4" of display group "009" is lower than that in display zones "1" of display group "010", check Evaporator Vent Temperature Sensor G263, Left Vent Temperature Sensor G150 and Right Vent Temperature Sensor G151 for proper installation and contact resistance at electrical connections and replace defective sensor if necessary.
  • - If no malfunction is found at the Left Vent Temperature Sensor G150 or the Right Vent Temperature Sensor G151 and at the Left Temperature Flap Motor V158 or the Right Temperature Flap Motor V159, perform measures to be taken in the event of temperature increase downstream of evaporator → Identifying malfunctions at temperature increase behind condenser .